| Test Standards |
BS476:Part 20 and Part 22 1987
MS 1073:Part 3:1996
ISO 9002:1994 |
| Specifications for Standard Fire Rated Door set includes: |
| Door Leaf |
44mm thick leaf formed from 1.1mm thick electro galvanised
steel skins reinforced with internal stiffener , fully insulated with
32kg/m3 rock wool, complete with preparation for locks,
reinforcement plates for door closer and hinge pocket. |
| Door Frame |
1.5 mm thick electro galvanised steel, seamless welded complete
with mortar boxes, preparation for hinge, door-closer and strike
plate. Standard Single and Double Rebate profile. |
| Finish |
Primer etching based coats only unless otherwise specified. |
| Hardware |
Provided as standard 4 hinges,
door closer and mortise lock set with lever handle. |
| Double-Leaf |
Equal or unequal door leaves are available |
| Maximum Sizes |
Door frame sizes Width x Height (mm)
Single Leaf 1100 x 2400mm
Double Leaves 2200 x 2400mm |
| Acoustic Performance |
STC 41 to 45 tested in accordance to ASTM E90 |
| Opening |
Wall
Rating |
Door and
Frame Rating |
Description and Use |
 |
4 Hour |
3 Hour
(180 minutes) |
These openings are in walls that separate buildings or divide
a single building into designated fire areas. |
 |
2 Hour |
1-1/2 Hour
(90 minute) |
Openings of this type are used in enclosures of vertical
communication or egress through buildings. Examples of these types of openings include stairwells and elevator shafts. |
 |
1 Hour |
1 Hour
(60 minute) |
These door and frame assemblies divide occupancies in a building. |
 |
1 Hour |
3/4 Hour
45 minute) |
For use where there are openings in corridors or room partitions. |
 |
2 Hour |
1-1/2 Hour
(90 minute) |
This opening is in a wall where there is the potential for severe
fire exposure from the exterior of the building. |
 |
1 Hour |
1-1/2 Hour
(90 minute) |
This opening is in an exterior wall that has the potential to be
exposed to moderate to light fire from the exterior of the building. |
 |
1 Hour |
1/3 Hour
(20 minute) |
These openings are in corridors where smoke and draft control
is required. The minimum wall rating is 1 hour . |